Reference Denver Water Engineering Standard Details: 33270
- Service line is perpendicular to the curb-line.
- Stop box and meter pit are in landscaped area, and match finished grade.
- Permanent obstructions are 5 feet clear of the meter vault:
- Utilities, street lights, foundations, fence lines, retaining walls, backflow prevention assemblies.
- Plantings, shrubs and branches must remain 2 feet clear of the meter vault lid.
- Permanent obstructions are 5 feet clear of the meter vault:
- Service line has no bends or connections until 5 feet downstream of the meter vault.
- Manhole cover is offset over the access ladder.
- Stop box is 2 to 5 feet from outside wall of meter vault.
- Service line depth is between 54 and 72 inches.
- Stop box is plumb and centered over the curb valve.
- Manhole concrete riser collar(s) plus manhole ring do not exceed 18 inches.
- Service line vault penetrations are grouted.
- Concrete support blocks and yoke support rods are installed.
- Concrete base beam installed.